In forceAcoustics & Access
Approved Document K: Protection from falling, collision and impact
Stairs, ramps, guarding and windows
Guidance on safe stairs, ramps, guarding, windows and vehicle barriers to reduce falls, collisions and impacts, including the minimum headroom over stairs and landings.
Also known as: AD K, Approved Document K, guarding
Key requirements
- General headroom over stairs and landings: at least 2.0m measured vertically from the pitch line of a flight and from the landing surface.
- Buildings other than dwellings, and common access areas in blocks of flats, need 2.0m clear headroom on escape routes, except at doorways.
- Loft conversions in dwellings may use the reduced headroom profile in Diagram 1.4 where 2.0m cannot be achieved: 1.9m, with a 1.8m zone over half the stair width.
- Worked conversions: 230cm = 2300mm = 2.3m (above the 2.0m general minimum); 180cm = 1800mm = 1.8m (below it, and only the loft-conversion relief uses 1.8m).
- Sets stair and ramp geometry, including rise, going and headroom.
- Guarding is required to floors, roofs, balconies and openable windows.
- Applies to new work and alterations, including changes of use.
Performance at a glance
- General headroom
- ≥ 2.0m over flights and landings
- Loft conversion relief
- 1.9m with a 1.8m half-width zone
- Worked conversions
- 230cm = 2.3m; 180cm = 1.8m
- Escape routes (non-domestic)
- 2.0m clear, except doorways
- Scope
- Stairs, ramps, guarding, windows
Applies to
New buildings, extensions and alterations in England.